Detail
VIRA D-SML 1000 is a low level limiter set for steam boilers. The system consists of the D-SMK 1000 Low Level Limiter Controller and the SMLD 1000 Low Level Limiter Probe. It provides reliable low water level monitoring and alarm protection, helping to support safe boiler operation when the water level reaches a critical low condition.
Low Water Level Protection
The D-SML 1000 monitors the boiler water level and generates an alarm signal when a low water level condition is detected. This enables the required protective action to be taken and helps prevent risks associated with insufficient boiler water level.
Fail-Safe and Self-Monitoring Architecture
The system uses a fail-safe, redundant and self-monitoring architecture. Its operating condition is continuously monitored, supporting fault detection for open circuit, short circuit, leakage and probe contamination conditions.
Clear Indication and Operator Functions
The D-SMK 1000 controller operates on 24VDC and features a 7-segment display for clear status and alarm indication. Dedicated test and reset functions support routine functional checks and controlled operator action following an alarm condition.
Flexible Installation
The controller can be installed in DIN rail or panel-mount configurations, supporting integration into different boiler control panel designs.
Suitable for Unattended Boiler Rooms
Its self-monitoring structure and fault detection functions make the D-SML 1000 suitable for steam boiler installations designed for up to 72 hours of unattended operation, subject to the requirements of the complete boiler system and local regulations.
Key Features
- D-SMK 1000 Low Level Limiter Controller and SMLD 1000 Low Level Limiter Probe
- 24VDC supply
- Low water level alarm and limiter function
- Fail-safe, redundant and self-monitoring architecture
- Open circuit, short circuit, leakage and contamination fault monitoring
- 7-segment display
- Test and reset functions
- DIN rail and panel-mount installation options
- Suitable for boiler rooms designed for up to 72 hours of unattended operation
| Controller | : | D-SMK 1000 Low |
| Supply Voltage | : | 24VDC |
| Functions | : | Self Monitoring Low Level |
| Input | : | Level Probe Input (Ct1, Ct1), Ground |
| Outputs | : | 1 Safety Relay, 1 Alarm Relay |
| Display | : | 7 Segment |
| Button | : | 4 Pieces (Test, Reset, Menü, Set) |
| Max. Ambinent Temp. | : | 55 ºC |
| Enclosure | : | PC |
| Type | : | Panel and Dın Rail |
| IP Class | : | IP 40 |
| Probe | : | SMLD 1000 |
| Connection and Size | : | Threaded - G1/2'' BSPT (Optional NPT) |
| Nominal Pressure | : | PN 40 |
| Length | : | 500-1000-1500 mm |
| Max. Operat. Press. | : | 32 Bar g |
| Max. Operat. Temp. | : | 239 ºC |
| Max. Ambinent Temp. | : | 75 ºC |
| The length of the probe can be cut to desired level |