Detail
ViraDeg vacuum degassers are installed in a bypass in the main flow of heating and cooling systems. Part of the system fluid is temporarily placed in a vacuum. Gases dissolved in the fluid are released, separated and removed from the system. Reintroducing the degassed fluid into the system allows it to absorb further free air pockets from the circuit. Air-free installation fluid ensures optimum system performance, and also greatly reduces commissioning times. Besides realising optimised system efficiency, all standard ViraDeg models save extra energy thanks to the integrated SmartSwitch. This device ensures that the degasser is only operational when necessary.
Model | V6 |
Pump brand | 6.0 barg |
Empty weight | 50 |
Vessel (stainless) | 7.0 lt |
Max. Glycol | 40% |
Connection ( inlet/outlet ) | 1/2" female |
Noise level | 56 db (A) |
System pressure | 1.0 - 6 bar |
Ambient temperature | 1 - 55°C |
Temperature system fluid | - 20 / 90°C |
Temperature refill fluid | 1 - 90°C |
Refill volume ( l/h) | 180 l/h |
Supply voltage ( 50-60 Hz) | 220-240 V |
Power supply | 0.75 kW |
Nominal current | 4.9 A |
Capacity ( pressure < 2 bar ) | 780 lt / h |
Capacity ( pressure > 2 bar ) | 1000 lt / h |
Protection class |
Model | V3 |
Pump brand | Grundfos |
Max. Pressure | 3.8 barg |
Empty weight | 40 |
Vessel (stainless) | 5.5 lt |
Max. Glycol | 40% |
Connection ( inlet/outlet ) | 1/2" female |
Noise level | 50 db(A) |
System pressure | 0.5 - 3.8 bar |
Ambient temperature | 1 - 55°C |
Temperature system fuid | - 20 / 90°C |
Temperature refill fluid | 1 - 90°C |
Refill volume ( l/h) | 180 l/h |
Supply voltage ( 50-60 Hz) | 220-240 V |
Power supply | 0.67 kW |
Power supply | 0.67 kW |
Nomil currenna | 4.0 - 4.4 A |
Capacity ( pressure < 2 bar ) | 600 lt / h |
Capacity ( pressure > 2 bar ) | 800 lt / h |
Protection class | IP 54 |